- Contact Person : Mr. Cao Steven
- Company Name : Baoding Kingrun Technology Co., Ltd.
- Tel : 00852-0312-3335059
- Fax : 00852-0312-3332659
- Address : Hebei,Baoding City,2#buding torch park industry park;677# Jingxiu street,baoding city,hebei province
- Country/Region : China
- Zip : 071000
JYT- A Transformer turns ratio tester
Visual test voltage ratio and group, Z mode test, CVT voltage ratio testing.
1. Widely test rating maximum is 10000, automatic testing.
2. High speed test, it can finish test for three-phase, error, connection group, tap value in 10 seconds.
3. CVT turns ratio testing.
4. Protective functions when the high and low voltage side made upside down.
5. Protective functions when the short circuit of the transformer and the inter-turn short circuit.
6. Can test and distinguish transformer with Z shape connection.
7. 160V and 10V output switch, it can test transformer of low rated voltage with non-load current strong.
8. Print output.
9. Small volume, lightweight.
Technical Index
Out put voltage: AC160V AC10V
1. Rating: 0.9~ 10000 0.9 ~ 200
2. Accuracy: 0.1% (below 500)
0.2% (500-3000) 0.3% (below 200)
0.5% (above 3000)
3. Resolution: Minimum is: 0.0001
4. Angle minimum resolution: 0.1 degree
4. Working power supply: AC220V±10% 50Hz
5. Applied temperature: -20°C~40°C
6. Contrary humidity: ≤90%, no dewfall
7. Dimension: 390mm x 230mm x 240mm
8. Weight: 6kgs
JYT- A Transformer turns ratio tester